What all 191 ABB ACS580 VFD fault codes mean, in plain words, with a risk grade for each. These come from the manufacturer's own manual. The fix for each one is in WERCS Diagnose.

Get the fixes · plans from $49/moUpdated November 4, 2026
CodeWhat it meansRisk
1080Backup/Restore timeout
The control panel or PC tool failed to communicate during a backup or restore, stopping the process.
YELLOW
1081Rating ID fault
The drive software cannot read the rating ID, which causes the drive to fault and stop.
YELLOW
2281Calibration
The measured offset of the output phase current is too great, causing the drive to stop.
YELLOW
2310Overcurrent
The output current has exceeded the internal fault limit, which causes the drive to stop operating.
RED
2330Earth leakage
The drive has detected a load unbalance from an earth fault, causing it to stop the motor.
RED
2340Short circuit
A short circuit has occurred in the motor or its cables, causing the drive to stop immediately.
RED
2381IGBT overload
The internal temperature is excessive due to an overload, which causes the drive to stop for protection.
RED
3130Input phase loss
The internal DC voltage is oscillating due to a missing input phase, causing the drive to stop.
YELLOW
3181Wiring or earth fault
The input power and motor cables are connected incorrectly, which prevents the drive from operating safely.
RED
3210DC link overvoltage
The intermediate circuit DC voltage is excessive, which causes the drive to stop to protect itself.
RED
3220DC link undervoltage
The intermediate circuit DC voltage is too low, which causes the drive to stop operating.
YELLOW
3381Output phase loss
A motor circuit fault has occurred because the output phases are disconnected, stopping the drive.
YELLOW
4110Control board temperature
The control unit temperature is too high, which causes the drive to stop working.
RED
4210IGBT overtemperature
The estimated drive IGBT temperature is excessive, causing the drive to shut down.
RED
4290Cooling
The drive module temperature is excessive, which forces the drive to stop operating.
RED
42F1IGBT temperature
The drive IGBT temperature is excessive, which causes the drive to stop running.
RED
4310Excess temperature
The power unit module temperature is excessive, causing the drive to shut down.
RED
4380Excess temperature difference
A high temperature difference exists between the IGBTs of different phases, stopping the drive.
RED
4981External temperature 1
The first measured external temperature has exceeded its fault limit, stopping the drive.
RED
4982External temperature 2
The second measured external temperature has exceeded its fault limit, stopping the drive.
RED
4990CPTC-02 not found
The extension module is not detected in the second option slot, stopping the drive.
YELLOW
4991Safe motor temperature
The extension module indicates a high motor temperature or disconnected thermistor, stopping the drive.
RED
5080Fan
The cooling fan feedback is missing on larger frames, causing the drive to stop.
YELLOW
5081Auxiliary fan broken
An auxiliary cooling fan is stuck or disconnected, which causes the drive to stop.
YELLOW
5089SMT circuit malfunction
A safe motor temperature fault is generated without a corresponding event, stopping the drive.
YELLOW
5090STO hardware failure
The safe torque off diagnostics detected a hardware failure, causing the drive to stop.
RED
5091Safe torque off
The safe torque off function is active due to a broken safety circuit signal, stopping the drive.
RED
5092PU logic error
The power unit memory has cleared, which forces the drive to stop operating.
YELLOW
5093Rating ID mismatch
The drive hardware does not match the information stored in memory, stopping the drive.
YELLOW
5094Measurement circuit temperature
A problem exists with the internal temperature measurement, causing the drive to stop.
YELLOW
5098I/O communication loss
The drive will stop functioning properly due to a communication failure with the standard input and output modules.
YELLOW
50A0Fan
The cooling fan is stuck or disconnected, which causes the drive to overheat and shut down.
YELLOW
5681PU communication
Communication errors are detected between the control unit and power unit, stopping the drive.
YELLOW
5682Power unit lost
The connection between the drive control unit and the power unit is lost, stopping the drive.
YELLOW
5691Measurement circuit ADC
A measurement circuit fault has occurred, which causes the drive to stop operating.
YELLOW
5692PU board powerfail
A power unit power supply failure has occurred, which causes the drive to stop.
YELLOW
5693Measurement circuit DFF
A measurement circuit fault has occurred inside the drive, which forces the equipment to shut down safely.
YELLOW
5697Charging feedback
The charging feedback signal is missing, which causes the drive to fault and stops the booth equipment.
YELLOW
5698Unknown PU fault
The power unit logic generated an unknown fault, which forces the drive to shut down the booth motor.
YELLOW
6181FPGA version incompatible
The firmware and FPGA versions are incompatible, which causes the drive to stop.
YELLOW
6200Checksum mismatch
The actual parameter checksums do not match the approved parameter checksums, which causes the drive to issue a mismatch fault.
YELLOW
6306FBA A mapping file
A fieldbus adapter mapping file read error has occurred, causing the drive to stop.
YELLOW
6481Task overload
An internal task overload fault has occurred, which causes the drive to stop.
YELLOW
6487Stack overflow
An internal stack overflow fault has occurred, which causes the drive to stop.
YELLOW
64A1Internal file load
An internal file read error has occurred, which forces the drive to stop.
YELLOW
64A4Rating ID fault
A rating ID load error has occurred, which causes the drive to stop.
YELLOW
64A6Adaptive program
An error occurred while running the adaptive program, which causes the drive to stop.
YELLOW
64B1Internal SSW fault
An internal software fault has occurred, which forces the drive to stop operating.
YELLOW
64B2User set fault
Loading the user parameter set failed due to incompatibility or missing data, stopping the drive.
YELLOW
64B3Macro parameterization error
Macro parameterization failed due to an invalid parameter write attempt, stopping the drive.
YELLOW
64E1Kernel overload
An operating system kernel overload error has occurred, causing the drive to stop.
YELLOW
64FFFault reset
A previous fault has been cleared from the control panel or network, which allows the drive to start the booth.
GREEN
6581Parameter system
A parameter load or save operation has failed, which causes the drive to stop.
YELLOW
6591Backup/Restore timeout
A control panel failed to communicate during a backup or restore operation, stopping the drive.
YELLOW
65A1FBA A parameter conflict
The drive lacks a functionality requested by the PLC, causing the drive to stop.
YELLOW
6681EFB comm loss
A communication break occurred in the embedded fieldbus, which causes the drive to stop.
YELLOW
6682EFB config file
The embedded fieldbus configuration file could not be read, causing the drive to stop.
YELLOW
6683EFB invalid parameterization
The embedded fieldbus parameter settings are inconsistent or incompatible, causing the drive to stop.
YELLOW
6684EFB load fault
The embedded fieldbus protocol firmware could not be loaded, causing the drive to stop.
YELLOW
6685EFB fault 2
An embedded fieldbus protocol application fault has occurred, which causes the drive to stop.
YELLOW
6686EFB fault 3
A fault reserved for the embedded fieldbus protocol application has occurred, causing the drive to stop the booth.
YELLOW
6882Text 32-bit table overflow
An internal text table overflow fault has occurred, causing the drive to stop.
YELLOW
6885Text file overflow
An internal text file overflow fault has occurred, which causes the drive to stop.
YELLOW
7081Control panel loss
The active control panel or PC tool has ceased communicating, stopping the drive.
YELLOW
7082I/O module comm loss
Communication between the IO module and the drive is failing, stopping the drive.
YELLOW
7085Incompatible option module
An unsupported fieldbus option module is detected, which causes the drive to stop.
YELLOW
7086AI Overvoltage
An overvoltage was detected on an analog input, which causes the drive to stop.
RED
7121Motor stall
The motor is operating in a stall region due to excessive load, stopping the drive.
YELLOW
7122Motor overload
The motor current is too high, which causes the drive to stop operating.
YELLOW
7181Brake resistor
The brake resistor is broken or not connected, which causes the drive to stop.
YELLOW
7183BR excess temperature
The brake resistor temperature has exceeded its fault limit, causing the drive to stop.
RED
7191BC short circuit
A short circuit exists in the brake chopper IGBT, causing the drive to stop.
RED
7192BC IGBT excess temperature
The brake chopper IGBT temperature has exceeded its internal limit, stopping the drive.
RED
7310Overspeed
This fault means the motor is turning faster than the highest allowed speed, causing the drive to stop the equipment.
YELLOW
73B0Emergency ramp failed
An emergency stop did not finish within the expected time, stopping the drive.
YELLOW
73F0Overfrequency
The maximum allowed output frequency has been exceeded, which causes the drive to stop.
YELLOW
7510FBA A communication
Cyclical communication with the fieldbus adapter module is lost, causing the drive to stop.
YELLOW
8001ULC underload fault
A signal has been under the user underload curve too long, stopping the drive.
YELLOW
8002ULC overload fault
A signal has been over the user overload curve too long, stopping the drive.
YELLOW
80A0AI supervision
An analog signal is outside the specified limits, which causes the drive to stop.
YELLOW
80B0Signal supervision 1
A fault was generated by the first signal supervision function, stopping the drive.
YELLOW
80B1Signal supervision 2
A fault was generated by the second signal supervision function, stopping the drive.
YELLOW
80B2Signal supervision 3
A fault was generated by the third signal supervision function, stopping the drive.
YELLOW
80B3Signal supervision 4
A fault was generated by the fourth signal supervision function, stopping the drive.
YELLOW
80B4Signal supervision 5
A fault was generated by the fifth signal supervision function, stopping the drive.
YELLOW
80B5Signal supervision 6
A fault was generated by the sixth signal supervision function, stopping the drive.
YELLOW
9081External fault 1
A fault has occurred in the first external device, causing the drive to stop.
YELLOW
9082External fault 2
A fault has occurred in the second external device, causing the drive to stop.
YELLOW
9083External fault 3
A fault has occurred in the third external device, causing the drive to stop.
YELLOW
9084External fault 4
A fault has occurred in the fourth external device, causing the drive to stop.
YELLOW
9085External fault 5
A fault has occurred in the fifth external device, causing the drive to stop.
YELLOW
A2A1Current calibration
The current offset and gain measurement calibration will occur at the next start, which delays the booth equipment slightly.
GREEN
A2B1Overcurrent
The output current has exceeded the internal fault limit, which triggers a warning while the booth equipment continues to run.
RED
A2B3Earth leakage
The drive has detected a load unbalance due to an earth fault, which triggers a warning without stopping the booth.
RED
A2B4Short circuit
A short circuit has been detected in the motor or cables, which triggers a warning while the equipment keeps running.
RED
A2BAIGBT overload
The transistor junction temperature is excessive, which triggers a warning to protect the components while the booth continues operating.
RED
A3A1DC link overvoltage
The intermediate circuit direct current voltage is too high while stopped, which prevents the drive from starting the booth.
RED
A3A2DC link undervoltage
The intermediate circuit direct current voltage is too low while stopped, which prevents the drive from starting the equipment.
GREEN
A3AADC not charged
The voltage of the intermediate direct current circuit has not reached operating level, which prevents the booth from starting.
GREEN
A490Incorrect temperature sensor setup
The temperature cannot be supervised due to an incorrect adapter setup, which triggers a warning on the drive display.
GREEN
A491External temperature 1
The first measured external temperature has exceeded its warning limit, which alerts the operator without stopping the booth equipment.
GREEN
A492External temperature 2
The second measured external temperature has exceeded its warning limit, which alerts the operator while the booth continues running.
GREEN
A4A0Control board temperature
The control unit temperature is too high, which triggers a warning while the drive continues to operate the booth.
RED
A4A1IGBT overtemperature
The estimated drive transistor temperature is excessive, which generates a warning without stopping the booth equipment from running.
RED
A4A9Cooling
The drive module temperature is excessive, which triggers a cooling warning while the booth equipment continues to operate.
RED
A4B0Excess temperature
The power unit module temperature is excessive, which causes the drive to shut down the equipment.
RED
A4B1Excess temperature difference
There is a high temperature difference between the insulated-gate bipolar transistors of different phases, which causes the drive to stop.
RED
A4F6IGBT temperature
The drive insulated-gate bipolar transistor temperature is excessive, which causes the equipment to stop running.
RED
A581Fan
The cooling fan feedback signal is missing, which triggers a warning while the drive continues to run the booth.
GREEN
A582Auxiliary fan missing
The internal auxiliary cooling fan is stuck or disconnected, which causes the drive to stop.
GREEN
A5A0Safe torque off
The safe torque off function is active because a safety circuit signal is lost, causing the drive to stop.
RED
A5EAMeasurement circuit temperature
There is a problem with the internal temperature measurement of the drive, which causes the equipment to stop.
GREEN
A5EBPU board powerfail
A power unit power supply failure has occurred, causing the drive to shut down.
GREEN
A5EDMeasurement circuit ADC
A measurement circuit fault has occurred, which causes the drive to stop operating.
GREEN
A5EEMeasurement circuit DFF
A measurement circuit fault has occurred, which causes the drive to stop operating.
GREEN
A5EFPU state feedback
The state feedback from the output phases does not match the control signals, causing the drive to stop.
GREEN
A5F0Charging feedback
The charging feedback signal is missing, which causes the drive to stop running.
GREEN
A682Flash erase speed exceeded
The flash memory has been erased too frequently and compromised its lifetime, causing the drive to fault.
GREEN
A686Checksum mismatch
The actual parameter checksums do not match the approved checksums, which prevents the drive from operating.
GREEN
A6A4Motor nominal value
The motor parameters are set incorrectly and the drive is not dimensioned correctly, preventing the motor from starting.
GREEN
A6A5No motor data
The required motor parameters have not been set, which prevents the drive from starting the motor.
GREEN
A6A6Voltage category unselected
The voltage category has not been defined, which prevents the drive from operating the motor.
GREEN
A6A7System time not set
The system time is not set, meaning timed functions cannot be used and fault log dates will be incorrect.
GREEN
A6B0User lock is open
The user lock is open and configuration parameters are visible, which triggers a warning on the drive.
GREEN
A6B1User pass code not confirmed
A new user pass code was entered but not confirmed, which triggers a warning on the drive.
GREEN
A6D1FBA A parameter conflict
The drive lacks or has not activated a functionality requested by the PLC, causing a communication fault.
GREEN
A6E5AI parametrization
The hardware setting of an analog input does not match the parameter settings, causing the drive to fault.
GREEN
A6E6ULC configuration
A user load curve configuration error has occurred, which causes the drive to stop operating.
GREEN
A780Motor stall
The motor is operating in a stall region due to excessive load or insufficient power, causing the drive to stop.
GREEN
A783Motor overload
The motor current is too high, which causes the drive to stop to protect the equipment.
GREEN
A784Motor disconnect
All three output phases are disconnected from the motor, which prevents the drive from running it.
GREEN
A793BR excess temperature
The brake resistor temperature has exceeded its warning limit, which triggers an alert on the drive.
RED
A794BR data
The brake resistor data has not been provided, which prevents the drive from operating correctly.
GREEN
A79CBC IGBT excess temperature
The brake chopper temperature has exceeded its internal warning limit, triggering an alert on the drive.
RED
A7A2Mechanical brake opening failed
The mechanical brake acknowledgement status is incorrect during opening, which causes the drive to stop.
GREEN
A7ABExtension I/O configuration failure
The installed module does not match the configuration or communication was disturbed, which stops the drive from operating.
GREEN
A7C1FBA A communication
Communication between the drive, PLC, and fieldbus adapter module is lost, causing the drive to stop.
GREEN
A7CEEFB comm loss
A communication break has occurred in the embedded fieldbus, which causes the drive to stop operating.
GREEN
A7EEPanel loss
The active control panel or PC tool has stopped communicating, which causes the drive to shut down.
GREEN
A88FCooling fan
The cooling fan maintenance timer limit has been exceeded, triggering a warning on the drive.
GREEN
A8A0AI supervision
An analog signal is outside the specified limits, which triggers a warning on the drive.
GREEN
A8A1RO life warning
The relay has changed states more than the recommended number of times, which triggers a life warning on the drive.
GREEN
A8A2RO toggle warning
The relay output is changing states faster than recommended, which triggers a toggle warning because the relay lifetime will be exceeded shortly.
GREEN
A8B0ABB Signal supervision 1
A warning has been generated by the signal supervision function one, alerting the operator without stopping the drive.
GREEN
A8B1ABB Signal supervision 2
A warning has been generated by the signal supervision function, which alerts the operator but allows the booth to run.
GREEN
A8B2ABB Signal supervision 3
A warning has been generated by the third signal supervision function, which alerts the operator without stopping the booth.
GREEN
A8B3ABB Signal supervision 4
A warning has been generated by the signal supervision function four, which alerts the operator without stopping the drive.
GREEN
A8B4ABB Signal supervision 5
The drive issues a warning generated by the internal signal supervision function five.
GREEN
A8B5ABB Signal supervision 6
A warning has been generated by the signal supervision function six, alerting the operator without stopping the drive.
GREEN
A8BEULC overload warning
The selected signal has exceeded the user overload curve, which triggers a warning on the drive.
GREEN
A8BFULC underload warning
The selected signal has fallen below the user underload curve, which triggers a warning on the drive.
GREEN
A981External warning 1
A fault has occurred in external device one, which triggers a warning on the drive.
GREEN
A982External warning 2
A fault has occurred in external device two, which triggers a warning on the drive.
GREEN
A983External warning 3
A fault has occurred in external device three, which triggers a warning on the drive.
GREEN
A984External warning 4
A fault has occurred in external device four, which triggers a warning on the drive.
GREEN
A985External warning 5
A fault has occurred in external device five, which triggers a warning on the drive.
GREEN
AF88Season configuration warning
A season has been configured to start before the previous season, which triggers a warning on the drive.
GREEN
AF90Speed controller autotuning
The speed controller autotune routine did not complete successfully, which prevents the drive from operating optimally.
GREEN
AFAAAutoreset
The drive indicates that an active fault is about to automatically clear itself.
GREEN
AFE1Emergency stop (off2)
The drive has received an emergency stop command, which causes the motor to coast to a stop.
GREEN
AFE2Emergency stop (off1 or off3)
The drive has received an emergency stop command, which causes the motor to ramp down and stop.
GREEN
AFE9Start delay
The start delay is active, meaning the drive will wait for a predefined time before starting the motor.
GREEN
AFEBRun enable missing
The run enable signal is missing, which prevents the drive from starting the motor.
GREEN
AFEDEnable to rotate
The signal to rotate was not received within the time delay, preventing the drive from starting.
GREEN
AFF6Identification run
A motor identification run is scheduled and will occur at the next start command.
GREEN
AFF8Motor heating active
Motor pre-heating is active and passing current through the motor, which keeps it warm before starting.
GREEN
B5A0STO event
The safe torque off function is active because a safety signal is lost, causing the drive to stop.
RED
B686Checksum mismatch
The actual parameter checksums do not match the approved checksums, which prevents the drive from operating.
GREEN
D401Max cleaning fault
The maximum number of cleanings was reached in the defined time, causing the automatic system to fail and the drive to fault.
YELLOW
D404Running dry
The dry run protection has been activated, which causes the drive to stop.
YELLOW
D405Pipe fill-timeout
The soft pipe fill reached its timeout limit without hitting the setpoint, causing the variable frequency drive to stop.
YELLOW
D40CCavitation detected
The system detects that the pump is not getting enough liquid, causing the variable frequency drive to stop running.
YELLOW
D501No more available PFC motors
No more pump control motors can be started because they are interlocked or in hand mode.
GREEN
D502All motors interlocked
All motors in the pump control system are interlocked, which prevents the drive from starting them.
GREEN
D503VSD controlled PFC motor interlocked
The motor connected to the drive is interlocked and unavailable, preventing it from running.
GREEN
D505Max cleaning warning
The maximum number of pump cleanings was reached within a defined time, which triggers a warning on the drive because the pump remains dirty.
GREEN
D506Pump cleaning not possible
The pump cleaning sequence cannot be started because the drive is not in remote control with an active start signal.
GREEN
D507Pump cleaning needed
Dirt detection indicates that the pump needs cleaning, but the automatic pump cleaning function is not allowed to start.
GREEN
D50ARunning dry
The dry run protection has been activated, which causes the drive to stop the pump.
GREEN
D50BPipe fill-timeout
The soft pipe fill has reached its timeout limit without hitting the setpoint, causing the drive to stop.
GREEN
D511Cavitation control
A cavitation control warning has been triggered, alerting the operator to potential pump issues.
GREEN
D58BGas pressure outside limits
The compressor gas pressure is outside the acceptable limits, which stops the drive from operating.
GREEN
D590Restart delay
A compressor restart delay is active, which prevents the drive from starting until the delay time has fully elapsed.
GREEN
D591Min. run time
The compressor minimum run time is active, which keeps the motor running until the time elapses.
GREEN
D602Cavitation tune completed
The cavitation auto tune process has finished successfully, which causes the drive to stop.
GREEN
FA81Safe torque off 1
The first safe torque off circuit is broken and active, which forces the variable frequency drive to stop the motor.
RED
FA82Safe torque off 2
The safe torque off function is active because circuit two broke, stopping the drive.
RED
FF61ID run
The motor identification run was not completed successfully, which causes the drive to stop.
YELLOW
FF63STO diagnostics failure.
An internal software malfunction occurred in the diagnostics, causing the drive to stop.
RED
FF81FB A force trip
A fault trip command was received through the fieldbus adapter, stopping the drive.
YELLOW
FF8EEFB force trip
A fault trip command was received through the embedded fieldbus interface, stopping the drive.
YELLOW

Every code comes from the manufacturer's own manual. Subscribers see which manual and page.