Burner controls, ignition and flame safeguards

Fireye MicroM Burner Control fault codes

What all 7 Fireye MicroM Burner Control fault codes mean, in plain words, with a risk grade for each. These come from the manufacturer's own manual. The fix for each one is in WERCS Diagnose.

CodeWhat it meansRisk
Lockout Intrlck OpenLockout Intrlck Open
The running interlock circuit was open when it needed to be closed, causing the control to lock out.
RED
Lockout Check ScannerLockout Check Scanner
The control detected a scanner problem like a defective shutter or false-firing UV tube and locked out the system.
RED
Lockout Check BLOWN FUSELockout Check BLOWN FUSE
No power was detected on terminal three due to a blown chassis fuse, causing the control to lock out.
RED
Lockout Flame Fail - AUTOLockout Flame Fail - AUTO
The burner locked out because the flame signal was lost during normal firing operation.
RED
Lockout Flame Fail - MTFILockout Flame Fail - MTFI
The burner locked out and shut off the fuel because the main flame was not detected during the main ignition trial.
RED
Lockout Flame Fail - PTFILockout Flame Fail - PTFI
The burner locked out and triggered an alarm because the pilot flame was not detected during the ignition trial.
RED
Lockout False Flame - STANDBYLockout False Flame - STANDBY
A false flame was detected during standby, causing the safety circuit to keep fuel valves closed and lock out the control.
RED

Every code comes from the manufacturer's own manual. Subscribers see which manual and page.