Burner controls, ignition and flame safeguards

Honeywell 7800 Series Burner Control (RM7800 / RM7840) fault codes

What all 8 Honeywell 7800 Series Burner Control (RM7800 / RM7840) fault codes mean, in plain words, with a risk grade for each. These come from the manufacturer's own manual. The fix for each one is in WERCS Diagnose.

CodeWhat it meansRisk
*Running ILK*Running ILK
The burner locked out because a required safety device in the running interlock circuit failed to close during prepurge.
RED
*High Fire Sw.*High Fire Sw.
The burner locked out because the control could not confirm the damper reached the fully open high fire position for purging.
RED
*Airflow Switch*Airflow Switch
The control did not get proof of proper combustion airflow during the prepurge cycle, which causes the burner control to fault.
RED
*Flame Detected*Flame Detected
The control saw an unexpected flame signal while the shutter was open during prepurge, which causes the burner control to lock out.
RED
*Main Flame Fail*Main Flame Fail
The burner locked out because the control module lost the main flame signal during normal operation.
RED
*Preignition ILK*Preignition ILK
The burner locked out because a preignition safety interlock was not in its expected state before starting.
RED
*Low Fire Sw. Off*Low Fire Sw. Off
The burner locked out because the control could not confirm the burner reached the low fire position during prepurge.
RED
*Pilot Flame Fail*Pilot Flame Fail
The burner locked out because the control module failed to detect a pilot flame during the ignition period.
RED

Every code comes from the manufacturer's own manual. Subscribers see which manual and page.