Burner controls, ignition and flame safeguards

Riello RDB 2.2 Burner Control (MO 535 - MPF) fault codes

What all 9 Riello RDB 2.2 Burner Control (MO 535 - MPF) fault codes mean, in plain words, with a risk grade for each. These come from the manufacturer's own manual. The fix for each one is in WERCS Diagnose.

CodeWhat it meansRisk
Red steady onReset button: steady red
The burner control locks out because no flame was established at the end of the safety time.
RED
Orange steady onReset button: steady orange
The burner control locks out due to a mains supply frequency error, stopping the heating system.
GREEN
Red blinking (0.5s/0.5s)Reset button: red blinking
The burner control locks out because a false flame or extraneous light signal was detected.
RED
Red fast blinking (0.2s/0.2s)Reset button: red fast blinking
The burner control locks out after reaching the maximum number of recycles due to repeated flame failures.
RED
Green + red blinking (0.5s/0.5s)Reset button: green and red blinking
The burner control locks out because it detects extraneous light or a false flame signal.
RED
Orange + green blinking (0.5s/0.5s)Reset button: orange and green blinking
The burner control locks out due to an internal memory error, preventing the burner from starting.
RED
Orange + green fast blinking (0.2s/0.2s)Reset button: orange and green fast blinking
The burner control locks out due to an internal voltage monitor error, preventing burner operation.
GREEN
Red + green inverted flashing (2.5s/0.5s)Reset button: red and green inverted flashing
The burner control locks out due to an internal control circuit fault driving the oil valve.
RED
Red + orange inverted flashing (2.5s/0.5s)Reset button: red and orange inverted flashing
The burner control locks out due to a fan motor error, stopping the combustion process.
RED