What all 11 Riello RDB 3.2 BT 50/70 Burner Control fault codes mean, in plain words, with a risk grade for each. These come from the manufacturer's own manual. The fix for each one is in WERCS Diagnose.

CodeWhat it meansRisk
Red steady onReset button: steady red
The burner control locks out because no flame was detected at the end of the safety time.
RED
Orange steady onReset button: steady orange
The burner control locks out due to a mains supply frequency anomaly, stopping the heating system.
GREEN
Red blinking (0.5s/0.5s)Reset button: red blinking
The burner control locks out because an extraneous light or parasite flame signal was detected.
RED
Red flashing (0.5s/2.5s)Reset button: red long-gap flashing
The burner control locks out because the oil pre-heater exceeded its maximum pre-heating time.
RED
Red fast blinking (0.2s/0.2s)Reset button: red fast blinking
The burner control locks out after reaching the maximum number of recycles from repeated flame failures.
RED
Green + red blinking (0.5s/0.5s)Reset button: green and red blinking
The burner control locks out because it detects extraneous light or a parasite flame signal.
RED
Orange + green blinking (0.5s/0.5s)Reset button: orange and green blinking
The burner control locks out due to an internal memory fault, preventing the burner from starting.
RED
Green + red fast blinking (0.2s/0.2s)Reset button: green and red fast blinking
The system detected an anomaly with the local or remote clearing button, which prevents the burner from operating.
GREEN
Orange + green fast blinking (0.2s/0.2s)Reset button: orange and green fast blinking
The burner control locks out due to an internal voltage fault, preventing burner operation.
GREEN
Red + green inverted flashing (2.5s/0.5s)Reset button: red and green inverted flashing
The burner control locks out due to a malfunction in the internal control circuit driving the oil valve.
RED
Red + orange inverted flashing (2.5s/0.5s)Reset button: red and orange inverted flashing
The burner control locks out due to a fan motor fault, stopping the combustion process.
RED