Burner controls, ignition and flame safeguards

Weishaupt W-FM 200 Combustion Manager fault codes

What all 16 Weishaupt W-FM 200 Combustion Manager fault codes mean, in plain words, with a risk grade for each. These come from the manufacturer's own manual. The fix for each one is in WERCS Diagnose.

CodeWhat it meansRisk
23Loc.c 23 / Err.c 23
The burner locks out because extraneous light was detected during the startup sequence.
RED
24Loc.c 24 / Err.c 24
The burner locks out because extraneous light was detected during the shutdown sequence.
RED
25Loc.c 25 / Err.c 25
The burner locks out because no flame was present at the end of the safety time.
RED
26Loc.c 26 / Err.c 26
The burner locks out because the flame failed while the system was in operation.
RED
27Loc.c 27 / Err.c 27
The air pressure switch sent an impermissible ON signal, which locks out the burner.
RED
28Loc.c 28 / Err.c 28
The air pressure switch sent an impermissible OFF signal, which locks out the burner.
RED
29Loc.c 29 / Err.c 29
The fan contactor sent an impermissible ON signal, which locks out the burner.
RED
2ALoc.c 2A / Err.c 2A
The fan contactor sent an impermissible OFF signal, which locks out the burner.
RED
2BLoc.c 2B / Err.c 2B
The flue gas recirculation air pressure switch sent an impermissible ON signal, which locks out the burner.
RED
2CLoc.c 2C / Err.c 2C
The flue gas recirculation air pressure switch sent an impermissible OFF signal, which locks out the burner.
RED
2DLoc.c 2D / Err.c 2D
The burner locks out because there is an impermissible on signal at the gas start release input.
RED
2ELoc.c 2E / Err.c 2E
The burner locks out because there is an impermissible off signal at the gas start release input.
RED
2FLoc.c 2F / Err.c 2F
The low gas pressure switch has reacted, which prevents the burner from operating.
RED
30Loc.c 30 / Err.c 30
The high gas pressure switch has reacted, which prevents the burner from operating.
RED
31Loc.c 31 / Err.c 31
The burner locks out because the valve proving test detected a leaking first valve or an unopened second valve.
RED
32Loc.c 32 / Err.c 32
The burner locks out because the valve proving test detected a leaking second valve or an unopened first valve.
RED

Every code comes from the manufacturer's own manual. Subscribers see which manual and page.